Closed Solicitation · DEPT OF DEFENSE
AI Summary
The Department of Defense is seeking a contractor for the redesign of a lift station at Robins Air Force Base. The project includes providing all necessary tools, materials, and labor for a system designed to transport hazardous liquid chemical waste. Key features include electric pumps, polypropylene tanks, and a stainless steel control panel.
The Contractor shall provide all the tools, parts, materials, equipment, labor, transportation, startup, and training for a redesigned lift station to the Commodities Maintenance Group (CMXG) at Robins Air Force Base (AFB), Georgia. These lift stations will be used to transport liquid chemical waste that could present environmental danger (i.e. acid waste, chrome waste).
Each Lift Station shall have the following features:
• Two (2) electric pumps made of CPVC or 316 Stainless Steel. Pump fittings must be CPVC with a two (2) inch maximum nominal size. The pump flowrate should be 25 gallons per minute per pump. The pump must have a 30-foot total dynamic head.
• The tank material shall be polypropylene, with a volume of 50 to 75 gallons and a single tank containment style.
• The dimensions of the lift station shall be four (4) feet long, three (3) feet wide, and four (4) feet high.
• The control panel enclosure shall be made of stainless steel.
• The power supply shall be 120V or 208V.
• Each pump shall have disconnect switches, hands-off-auto, and level sensors for automation on/off pump operation.