    AI Summary

    City of Port Neches seeks contractors for replacement of pneumatic butterfly valves with electric actuated valves at its water treatment plant clarifiers. Work includes valve removal, installation, electrical connections, support structures, and painting.

    Opportunity details

    Solicitation No.
    6980b371be0ca5df2c610555
    Type / RFx
    RFP
    Status
    Active
    Level
    city
    Published Date
    February 2, 2026
    Due Date
    February 18, 2026
    NAICS Code
    237110AI guide
    State
    Texas
    Agency
    City of Port Neches

    Description

    Clarifier No. 1 Blow Off Valve Replacements


    Replace three existing pneumatic actuated butterfly valves with new electric actuated
    butterfly valves.

    1. Coordinate with plant operators to remove existing clarifier from service.
    2. Abandon existing air piping. Plug existing piping at blower header.
    3. Remove existing pneumatic actuators and butterfly valves. Replace existing
    butterfly valves with new 4-inch Pratt 2FII AWWA Butterfly valves with Beck
    electric (open/close) actuators.
    4. New actuators will be powered with 120V from new 10 amp circuits in the
    existing Filter Valve Actuator Load Center located in the Filter Gallery.
    5. New actuators will be controlled using existing open/close control wiring from
    the Filter Control Room.
    Install support beam as shown mounted on top of existing concrete and support
    existing piping and new valves and fittings.
    Clean and paint all new and existing piping and valves.

    Clarifier No. 2 Blow Off Valve Replacements

    Replace three existing pneumatic actuated butterfly valves with new electric actuated
    butterfly valves.

    1. Coordinate with plant operators to remove existing clarifier from service.
    2. Abandon existing air piping. Plug existing piping at blower header.
    3. Remove existing pneumatic actuators and butterfly valves. Replace existing
    butterfly valves with new 3-inch Pratt 2FII AWWA Butterfly valves with Beck
    electric (open/close) actuators.
    4. New actuators will be powered with 120V from new 10 amp circuits in the
    existing Filter Valve Actuator Load Center located in the Filter Gallery.
    5. New actuators will be controlled using existing open/close control wiring from
    Filter Control Room.

    Install support beams and pipe supports as shown.  Remove existing grating and support angle as shown.  Remove and replace hand railing and install self closing gate.  Clean and paint all new and existing piping and valves.

    ## Details **Bid/Project ID:** B753-1033 **Type of Work:** Valve replacements **Pre-Bid Location:** City of Port Neches, City Hall Council Chambers, 1005 Merriman Street, Port Neches, TX 77651 **Bid Location:** City of Port Neches, City Hall, 1005 Merriman Street, Port Neches, TX 77651 **Engineer/Publisher:** LJA ENGINEERING, INC **Engineer Address:** 2615 Calder Ave, Ste 500, BEAUMONT, Texas, 77702

    Key dates

    1. February 2, 2026Published
    2. February 18, 2026Responses Due

    AI classification tags

    Frequently asked questions

    SLED stands for State, Local, and Education. These are solicitations issued by state governments, counties, cities, school districts, utilities, and higher education institutions — as opposed to federal agencies.

    SamSearch Platform

    Stop searching. Start winning.

    AI-powered intelligence for the right opportunities, the right leads, and the right time.