SLED Opportunity · WYOMING · WYOMING STATE CONSTRUCTION DEPARTMENT

    Dan Speas Fish Hatchery - Cool/Warm Water Facility Construction - Wyoming Game & Fish Department

    Issued by Wyoming State Construction Department
    localBidWyoming State Construction DepartmentSol. 207695
    Closed
    STATUS
    Closed
    due Feb 19, 2026
    PUBLISHED
    Posting date
    JURISDICTION
    Wyoming State
    local
    NAICS CODE
    236220
    AI-classified industry

    AI Summary

    Construction bid for Dan Speas Fish Hatchery cool/warm water facility in Casper, WY. Mandatory pre-bid meeting on Jan 13, 2026. Bids due Feb 19, 2026 via Public Purchase. 10% bid bond required for bids over $150,000. Extensive Q&A and addenda provided for technical clarifications.

    Opportunity details

    Solicitation No.
    207695
    Type / RFx
    Bid
    Status
    Active
    Level
    local
    Published Date
    Due Date
    February 19, 2026
    NAICS Code
    236220AI guide
    State
    Wyoming
    Agency
    Wyoming State Construction Department

    Description

    The Wyoming State Construction Department, Procurement Section, on behalf of the Wyoming Game and Fish Department, (Procuring Agency) will receive bids until 1:00 p.m. Mountain Time on February 19, 2026, through the Public Purchase online bidding system for the Dan Speas Fish Hatchery - Cool/Warm Water Facility Project, located at 8200 Speas Road, Natrona County, WY. Project Description: This project will consist of the construction of a new cool/warm water hatchery facility. A mandatory pre-bid meeting will be conducted at 10:00 a.m. MT on Tuesday, January 13, 2026 starting at Casper Regional Office, 3030 Energy Lane, Casper, WY, 82604, then proceeding to the project location at 8200 Speas Road, Casper, WY 82604. Bid documents available by logging on to Public Purchase at www.publicpurchase.com. Only bids submitted through the Public Purchase site and on State of Wyoming forms will be considered. It is the bidder's responsibility to review, through Public Purchase at www.publicpurchase.com for answers to questions, addenda, or bid tabulations. Telephone calls, emails, or faxes may not be accepted. Bidding questions shall be submitted on the Public Purchase website by 5:00 p.m. Mountain Time on January 27, 2026. All questions will be answered and provided to all prospective bidders via answers on the Public Purchase website or in the form of a written addendum posted on Public Purchase by 3:00 p.m. on February 4, 2026. Questions received after 5:00 p.m. Mountain Time on January 27, 2026, will not be addressed. It is the bidder's responsibility (not required) to add their company to the Plan Holders and Contractors List. Each bidder is required to have a bid deposit in the amount of Ten Percent (10%) of the total bid, if bid amount is greater than $150,000.00, which shall be in the form of a bid bond, cashier's check, or certified check (a copy of a check will not be accepted) drawn on a reliable bank and made payable to the State of Wyoming (no personal checks will be accepted), or an electronic bid bond with Surety 2000. ONLY if you are going to submit an original 10% bid bond or submit a 10% cashier check, it MUST be received in the Procurement Office at: Wyoming State Construction Department, Procurement Office, 700 West 21st Street, Cheyenne, Wyoming 82002, by 1:00 p.m. February 19, 2026. A COPY OF THE 10% CASHIER CHECK WILL NOT BE ACCEPTED. If you are using Surety 2000 you will need to upload with your bid response documents a copy of the Surety 2000 document. Procurement Representative: Lenora Simpson; Phone: (307) 777-3558 --- QUESTIONS AND ANSWERS --- Q: 1. Please clarify "vendor" attendance at pre-bid. Does this mean all potential subcontractors and vendors for the GC also have to be in attendance at the pre-bid, or is it just mandatory for the GC's A: GCs are required to attend. Subs/Vendors are welcome, but it's up to the GC if they want them to attend. Q: Is it possible to get the drawing file size reduced? The current size is far too large to be able to distribute the drawings via the normal procedures. The file is locked due to signatures so we are not able to reduce the file size on our end. A: WGFD will reach out to each bidder to provide a link to a Google Drive that will have the plans broke out by discipline and will be easier to distribute. Q: Is the project Geotechnical Report available? A: Yes. The Geotechnical report will be shared via the Google Drive that was mentioned in the answer to Question #2 above. Q: See comments from the MariSource Incubator mfr regarding some of the information contained in Spec Section 115316 Hello, Thank-you for bearing with me through all my questions. I have attached a quote above for one of our 16 Tray Trout Incubators. This incubator has a screen size that is 14 x 18 per square inch. I did see a spot in your document that says 12 x 12 per square inch. That would be our salmon incubator. If you would like a quote for that one instead, I am happy to update the quote. Additionally, I noticed that the materials that you have in your descriptions are materials that we no longer use. I have attached a document with more information on this. Please see below for correct materials. Tray Stand: * 6063-T52 Aluminum with ABS Side Panels * We do not use polyester resin reinforced with glass roving anymore as we now use ABS. * We do not offer floor mounting kits Incubation Trays: * The Water Tray and Egg Tray are made from polypropylene * The Egg Tray Lid is made from ABS * Both the egg tray and egg tray lid have a fiberglass mesh screen * The tray comes with a stainless-steel locking pin to secure the lid in place A: See forthcoming Bid Addendum #1 Q: Bid Form: Is the "build-out" of the building - i.e. office area, walls surrounding the various rooms to be included in Bid Item 4? A: No answer provided yet. Q: Sheet D101 Demo key note D mentions coordinating with WGFD for use of asphalt millings on the property elsewhere. Does this also apply to keynote A's concrete demo, or does that need to be hauled off site? A: Any demo associated with keynote A on Sheet D101 will be hauled off site. Q: Please confirm the insurance requirements for the project. No information is included in the project specifications and the sample contract had not been included in the original RFQ A: Insurance requirements can be found in the Sample Contract (Section 10.P and 10.Q) that is attached to the RFB documents. Q: Plan sheet C103 shows different exterior equipment pads to be provided around the building. Reference detail is S14/GS008. This detail is for stepped footing. Should the equipment pads be detail S15/GS008? A: Yes, the correct reference for the equipment pads on grade is S15/GS008 Q: Please confirm which "yard" piping to be included in Bid Item 13 vs Bid Item 15. (Is Bid Item 15 only for Septic/sanitary system, and Bid Item 13 would include all of the other system piping, or is Bid Item 13 only for the backwash piping associated with the Solids tank, and all other yard piping would be in Bid Item 15? A: See forthcoming Bid Addendum #1 Q: Plan Sheet A100 shows graphically what appears to be pipe bollards to be installed at the exterior corners of the RAS rooms, however on plan sheet A105, these are not called out by plan note. Are bollards required at these corners? A: See forthcoming Bid Addendum #1 Q: Can you elaborate on section 2 from table 51. on the RFB? Is there a template for the work plan? Is it related to self-perform work only? A: There is no specific template for the Work Plan. The intent of the Work Plan is to show your understanding of the project and the sequence of work and to show that you have carefully considered it as much as possible at the time of bidding. With the amount of Owner supplied equipment, it will be important for the Owner to have a good idea of your work plan to help coordinate timely equipment delivery. Q: Bid Schedule Clarifications: 1. Can you confirm if the angle iron and FRP grating should be included in Bid Item 03. If not, which Bid Item should it be allocated to? A: See forthcoming Bid Addendum #1 Q: Admin Locker Room Area (Room A007): No furnishings are shown to be provided/and or installed in this room. Is this by the Owner? A: Yes. Furnishings for Room A007 (Locker Room) will be furnished and installed by Owner Q: Generator Size: Drawing sheet E001 shows a 1800kW generator, but the specifications call out a 1500kW unit. Which is correct? A: 1500KW is correct. Q: 1. Elevations show 4' for main wall tile height, finish schedule shows 4'-6". Please clarify 2. Backsplash elevations show opposite layout as bathroom walls. Want to confirm this is correct. 3. Is Schluter Jolly to be installed between CT-1 and CT-2 to create a straight transition? 4. Grout color and type...epoxy or regular? A: See forthcoming Bid Addendum #1 Q: Would a "Schedule Narrative" suffice for the Work Plan? A: See the answer to Question 11. Also, as talked about at the pre-bid meeting, the Work Plan is not expected to be a detailed task list with firm dates. A detailed schedule will be required from the awarded Contractor. Q: Sheet GA004; Wall type S2 refers us to sheet GA006 for finish information. There is no GA006 in the set. Please advise. A: see forthcoming Bid Addendum #1 Q: Please clarify door type F. Under the door type schedule the picture shows a coiling door, but on the door schedule it is called out as an overhead door and not a coiling door. A: see forthcoming Bid Addendum #1 Q: Please advise if BABA is applicable to this project. Spec Section 11 53 16 - Incubators notes this requirement in Section 2.1 and directs bidders to review BABA requirements in Spec Section 01 60 00, but nothing is outlined in this Spec Section related to BABA requirements. Please advise. A: BABA provisions are NOT required on this project. Q: There is not a specific spec section for protective coatings (typically spec section 09 96 00). What are the specific requirements for any coating requirements on pump/piping. Plan Sheet G012 Notes 13 & 14 direct bidders to review project specifications. A: See Addendum No 2 Q: 1.Is there a model that can be made available to bidding contractors to assist with takeoff for views not shown in the project documents? 2. Section 09 96 00 is referenced in multiple sections but is not currently in the specifications. Can this be provided? 3. Section 40 23 21, 3.1B states "Piping shall be firmly supported with fabricated or commercial hangers or supports in accordance with section 15006-Pipe Supports". Should this reference be to section 40 23 12? If not, please provide section 15006. 4. Section 40 90 00, 2.4A states that contractor shall arrange for the manufacturers of the equipment and fabricators of panels and cabinets to allow the Owner's Representative and Owner to inspect and witness the testing of the equipment at the site of fabrication. Is the contractor to include the costs of travel, lodging, and food for this witness of factory testing or will this be paid by the Owner? 5. Item 15 in the RFB lists the attached documents. The list of Owner and Contractor supplied equipment and prevailing wage documents are missing. Please provide. 6. We are assuming the Drum Filter DF-603 is mislabeled. Specification tag number is DF-601. Please clarify. 7. Section 46 30 01. Please verify the tag numbers for the Gas Management Towers. Drawing tags are GCC-101 through GCC-601 and DG-001. Specification tags are LHO-1 through LHO-6 and CO2-1 through CO2-6. 8. In the Bid Schedule, Bid Item 9-Division 13-Special Construction-Light Room. There is no Owner supplied equipment listed in the description. Please verify if the drum filter, biofilter, and gas control will be Owner supplied for this bid item. 9. Section 46 21 33. Microscreen Drum Filters are identified in the RFB as Owner supplied. Please clarify which manufacturer was selected and provide the following information: approved submittal and installation instruction as well as anticipated delivery dates. 10. Section 46 21 34. Automatic Screen Filters are identified as Owner supplied. Please provide the EVOQUA approved submittal and installation instructions as well as anticipated delivery dates. 11. Section 46 30 01. Gas Management Towers are identified in the RFB as Owner supplied. Please clarify which manufacturer was selected and provide an approved submittal with installation instructions and anticipated delivery dates. 12. Section 46 33 93. Fiberglass Self-Cleaning Plastic Tanks are identified in the RFB as Owner supplied. Please provide the Oceans Design approved submittals with installation instructions and anticipated delivery dates. 13. Section 46 61 19. Fluidized Sand Biofilter is identified in the RFB as Owner supplied. Please clarify which manufacturer was selection and provide approved submittal with installation instructions and anticipated delivery dates. 14. Section 46 66 13. Ultraviolet Disinfector is identified in the RFB as Owner supplied. Please clarify with manufacturer was selected along with an approved submittal with installation instructions and anticipated delivery dates. A: see forthcoming Bid Addendum #1 for Answers to 21-1, 3,5-14 A: See Addendum No 2 for answers to 21-2 and 21-4 Q: The bid form calls for several breakouts that refer to "Owner Supplied Contractor Installed" equipment. Will you please identify said equipment that is to be contractor installed. A: see forthcoming Bid Addendum #1 Q: Bids will be disclosed on February 19th, 2026 even though the WG&FD has to take the matter to the commission for final approval, correct? A: see forthcoming Bid Addendum #1 Q: Who is responsible for the Construction Materials Testing? If both the owner and contractor are responsible for different tests please clarify which tests are to be by owner and which tests are to be by contractor. A: see forthcoming Bid Addendum #1 Q: Will the contractor get to use the owner's existing utilities for temporary utilities during the project. Electrical, water, gas, etc. A: see forthcoming Bid Addendum #1 Q: It is not typical for the PEMB supplier to supply anchorage or stairs. I assume using alternate steel suppliers for this is acceptable, please advise. A: See Addendum No 2 Q: We do not see any specifications for the sectional overhead doors. Please advise? A: See Addendum No. 2 Q: Reference sheet S102 the trench shown along grid line 7 has invert elevations called out as 5223.18 and 5222.93 on each end. Do these inverts included the 6" pitch shown on detail 1 on S503 or are they to the side elevations where the walls will be? Please advise. A: see forthcoming Bid Addendum #1 Q: What is the correct reinforcing for the slab. Sheet GS007 detail S8 shows a single and a double mat. Please advise. A: see forthcoming Bid Addendum #1 Q: On the mechanical schedule page GH004, FCU-900 and CU-900 are both spec'd as 410a Refrigerant. 410a equipment is no longer produced. May we get an updated spec for either R-32 or R-454b Refrigerant for those two pieces of equipment? A: See Addendum No. 3 Q: 1. Is EMT acceptable in the office space? MC Cable in walls and lighting? 2. Do they want corrosion resistant Unistrut and All Thread? Or is standard galvanized sufficient? 3. Devices on the hatchery floor do they need to be weather resistant? 4. Detail shows cable tray supported off suspension cables, but no information was provided? 5. Generator and ATS sizing 1500kW from the Specs or 1800kW from the drawings? 6. Is the owner going to start the process with RMP? Who is responsible for the RMP Costs? 7. Is Generac an Approved Equal? 8. H1E and H2E are called out in drawings, there is no fixture detail except for a note calling out battery backup. Do they have a specific battery? 9. There is no controls or power from the ATS and Panels to the Generator? 10. Is there a grounding detail? 11. Conduits are under sized for the Main Service. Does WGFD want conduits sized correctly or do they want to pricing according to drawings and have a CO? 12. Do we need to look into VFD cable? With the amount of VFDs the harmonics on the electrical system are going to be high and could cause issues with other equipment including Critical Systems? 13. Where does WGFD want dedicate space for IT Equipment? 14. Where does PP-5, XFMR-5, & LP-5 go? They are in the cable and conduit schedules, but they are not on the drawings? 15. Fire Alarm and Access Control? 16. Conference room, E801 Does WGFD want a floor box for the conference table? 17. Does WGFD want Low Point Drains installed on the conduit runs to facilitate draining? 18. Does WGFD want STL8 on conduit to condulet threads? Cold Zinc on all cuts? 19. Page E801 does WGFD want a recep behind the touchscreen SCADA Interface? 20. Does WGFD want basket tray for the Voice/Data in the Admin Area? 21. Does the ATS need to be Service Entrance Rated? OR does WGFD want to add a 1600A Main Disconnect? A: see forthcoming Bid Addendum #1 for answers to 31-2 and 6 A: See Addendum No. 2 for answers to 31-1, 31-4, 31-5, 31-7, 31-9 thru 31-14, 31-16 thru 31-21. We are still researching 31-3, 31-8, and 31-15. A: See Addendum No. 3 for answers to 31-8 and 31-15 A: See Addendum 4 for answer to 31-3 Q: Re: A601/A602 rooms P011, P012, P016, and P017 the shading calls for VTC, but the callout is APC. Please advise. There is also a note #1 on the callout referring to Epoxy Painted Finish, please advise. A: See Addendum No 2 Q: Please confirm that all exposed ceilings will not be painted other than the Effluent Treatment Room. A: See Addendum No.2 Q: Will we be able to utilize the existing onsite utilities for hooks of water and power? If so, do we need to meter them separately or will WYGFD pay for the costs of those charges directly? A: see forthcoming Bid Addendum #1 Q: Are the permitting fees through Natrona County by Owner? A: See Addendum No2 for more information Q: Is the project going to require a Building Information Modeling (BIM) effort for the MEP Systems? Or will this be at the contractor's discretion? A: See Bid Addendum #4 Q: Is QA/QC testing by owner? A: see forthcoming Bid Addendum #1 Q: 1.We are not seeing a substitution request form in the specifications. Can one be provided? 2. We have not seen a link to the Google Shared Drive. Can you please provide that? A: 2. Send an email request to loren.woodin1@wyo.gov for access to the Google shared drive. A: 1. A substitution request form has been added to the shared google drive (https://drive.google.com/drive/u/0/folders/0ANzrzbS0zXYbUk9PVA). It will also be included in the next bid addendum. Substitution requests can be emailed directly to loren.woodin1@wyo.gov and will be delivered to the correct personnel for review. Q: Please confirm that the Prevailing Wages included in Addendum 1 supercede the Prevailing Wages included in the original project bid documents. A: yes,confirmed Q: The addendum included two different prevailing wage rates for electricians. Assume we are to use "building construction" rates vs the "heavy highway rates". Please confirm. A: Confirmed. The Building Construction prevailing wages are correct for this project. Q: During review of the one-line diagram (Sheet E001), it was noted that the service entrance arrangement is not fully defined. For bidding purposes, we request confirmation of the intended configuration so that pricing reflects the correct equipment. 1. Combination CT Cabinet and Service Disconnect (Exterior) * For this size of service, Rocky Mountain Power requires a freestanding CT cabinet located outdoors. For bidding purposes, please confirm that the design intends for a combination CT cabinet and service entrance disconnecting means to be installed on the exterior of the building, ahead of all downstream equipment. 2. Non-Service-Entrance-Rated ATS * With a service entrance disconnect located outside the building, please confirm that the Automatic Transfer Switch (ATS) is intended to be provided as a standard, non-service-entrance-rated ATS. 3. Removal of 1600A Main Breaker in MDP * With the main disconnecting means located upstream in the combination CT/disconnect cabinet, please confirm that the 1600A main breaker shown in the MDP may be removed and that the MDP should be provided as main-lugs-only (MLO). 4. Performance testing of the ground fault protection system. * Please confirm that testing of the Service Entrance ground fault protection system required by NEC 230.95(C) is the responsibility of the electrical contractor. A: See Addendum No.2 Q: Are the unanswered items from questions #21, #31, and #38 going to be answered in an upcoming addendum? A: See Addendum No. 2 Q: I do have a couple questions just to verify since cable tray is made to order and labelled as NCNR. Nema VE 1 is not necessarily the nema rating, but more of the weight test rating standards they use. The PDF's are showing 18"W x 6"H which leads me to believe 6" side rail. But the spec does call out "4-inch, 6-inch, or as shown, inside depth" which leads me to believe 6" load depth. Can you please confirm if they are wanting 6" side rail or 6" load depth which is 7" side rail. A: See Addendum No. 2 Q: Please see attached Substitution Request for window shades A: see answer to question #45 Q: Do we submit substitution requests direct to Owner's rep since we cannot do attachments to questions on PublicPurchase? A: A substitution request form has been added to the shared google drive (https://drive.google.com/drive/u/0/folders/0ANzrzbS0zXYbUk9PVA). It will also be included in the next bid addendum. Substitution requests can be emailed directly to loren.woodin1@wyo.gov and will be delivered to the correct personnel for review. Q: Will you accept a NEMA 1 enclosure rather than a NEMA 12 for the MMCs? Also, is there an issue if the required space for the MCC exceeds that of what is shown on the drawings if wall space allows and proper clearances are met? A: See Addendum No. 2 Q: The Luminaire Schedule on Sheet E006 lists quantities for each fixture type. 1. Please confirm whether the quantities shown in the Luminaire Schedule are intended to be used for bidding purposes. 2. If there is a discrepancy between the fixture quantities shown on the Luminaire Schedule and those shown on the drawings, please clarify which source takes precedence for bidding and construction. Types H1 (emergency) and H2 (emergency) are missing from the fixture schedule. 1. Are these fixtures intended to have an integral battery or should they be powered from an emergency lighting inverter? 2. Alternately, can the generator be used to power these lights or is it being considered "optional standby" A: See Addendum No. 2 Q: 1. Please verify the tag numbers for the submersible sump pumps. Specification identify the Raceway Pumps as P-603, P-604. The equipment schedule, on GM001, tags are P-605, P-606. Specification identifies the Spraybar Supply Pump as P-108. The equipment schedule, on GM001, tag is P-008. 2. Specification 11 30 13 - Owner Provided Appliances - Owner is providing Cooking, Refrigeration, and Cleaning appliances and Trash compactors. Please provide a list of appliances, approved submittals, installation instructions and anticipated delivery dates, to be able to coordinate rough-ins, install and connection to required utilities. 3. Sheet M601 shows Ambient Water supply entering the building and appears drawn as PVC. The callout on this 12" header notes it as HDPE DR21. After the tee's off of this pipe the callout changes to PVC. Sheet M102 notes this header as PVC. Please confirm pipe material is intended to be PVC. 4. The location of the 3" backwash line is shown entering in a different location on sheet C112 than on M102 & M601. Please confirm which location this pipe is to enter the building. 5. Section A on M203 shows the 2" supply drop from the 4" AW line in to the RAS tank area. The 2" valve is shown with tag number V-264. This valve is not included in the valve schedule, however valves in similar applications are noted as V-ABC with is a 2" true union ball valve. Is this valve intended to be a 2" PVC true union ball valve? 6. Section A on M408 shows the 2" supply drop valves with tag numbers V-616 and V-617. These tags are also shown in a different location and the valve schedule notes them as 4". Please confirm these two valves are intended to be 2" true union ball valves not 4". 7. Sheet M602 shows supply and return piping exiting tank T-003 to the chilling system as well as tank T-002 to the heating system. Does the scope of supply of the two skid systems include the valves at the supply and discharge of the skids as well as the supply and discharge headers or should the contractor include these in our scope of supply? 8. Section 40 23 02 2.1.B notes wherever possible, pipes are to be supported from structural members, and where necessary to frame structural members between existing (engineered metal building) members, such supplementary members shall be provided by Contractor. Please confirm the loads for Electrical, HVAC, Plumbing, and process piping have been incorporated in to the design criteria on GS001 that establish the design loads for the preengineered metal building. 9. Sheet S401 - Please provide additional construction details for how the mezzanine is to be supported and attached to the floor and/or the preengineered metal building. A: See Addendum No.2 for answers to 48-1 thru 48-3, and 48-5 thru 48-9. We are still researching 48-4. A: See Addendum No. 3 for answer to 48-4 Q: Section 26 05 33.2.3 (B) 6 required large junction boxes to be NEMA Type 1, 3R, 4 or 4X per Section 20 01 00, but does not define which areas require NEMA 4 or 4X. Please clarify which rooms require NEMA 4 or 4X enclosures and also confirm that NEMA 1 is acceptable for all dry non washdown interior locations. A: See Bid Addendum #4 Q: Section 26 05 33 2.2(C) appears to require sealing locknuts on all locations. Please confirm that standard locknuts are acceptable for dry interior conditions. Section 2.2 (D) does not specify whether threadless fittings are allowed. Please confirm that threadless fittings are acceptable for indoor dry areas. A: See Bid Addendum #4 Q: Section 26 05 33 requires box covers to be secured with stainless steel screws. If 4" square boxes are allowed, is it the intent to have the contractor remove the factory provided 8-32 screws and replace them with stainless steel screws for all interior device and junction boxes? Please clarify where stainless steel screws are required. A: See Bid Addendum #4 Q: Section 26 05 33 2.3 A (1) appears to allow sheet metal boxes (e.g. 4" square) for dry interior uses. Section 2.3(a) 4 only lists FS/FD cast boxes. Please confirm where 4" square boxes are acceptable in dry interior locations. Please confirm whether FS/FD boxes are required only in wet/exterior/industrial areas. A: See Bid Addendum #4 Q: Addendum 2, Question 31 states EMT & MC Cable are not allowed and reference Section 26 05 33 for acceptable raceway types. Section 260533 does not list EMT as a permitted raceway. GRC/IMC appears to be the only practical listed alternative. Please confirm that the engineer intends for office/admin interior wall branch circuits to be installed using RMC/IMC. Section 3.2 of the same spec section notes that GRC is intended to be used where exposed, but there is no mention of raceways for concealed work. GRC/IMC in a concealed stud wall is not practical application and will add significant labor to the project. Will the engineer re-consider the answer to Question 31 and allow for EMT where concealed in walls or above ceilings? If EMT is unacceptable, is PVC ran in a concealed wall an acceptable alternate to PVC? A: See Bid Addendum #4 Q: Is there any chance they would want to install 6"x8" core filled block instead of installed concrete curb for their wall lines? Assumption is that this will look better in the end and save labor costs. That is an expensive option to then build walls on top of. A: At this stage, No. Bid the plans. Q: Mag meter spec calls for polypropylene liner material - McCrometer (approved manufacturer) uses 3M 135 Epoxy rated to 200 degrees F. Will this be acceptable? A: See Bid Addendum #4 Q: Electrical drawings show the vast majority of raceways being ran overhead in IMC. Would it be possible to run several raceways underslab in PVC? A: See Bid Addendum #4 Q: 1. Is there a specific reason Rockwell PLCs and Wonderware SCADA were selected? If Wonderware is important to the Owner, we recommend System Platform with AVEVA Historian with Dream report works well, not as certain as to InTouch system. 2. Are there any examples f what the HMI/SCADA should look like? Can more detail be provided for the requirements in Section 2.3C. Is it expected that the SCADA will be accessible in any location outside of the specified HMI? Will all control be handled by interfacing with the single HMI or are there any control requirements for accessing SCADA outside of this location? How many reports does the Owner require? are there any examples of what they are looking for? A: See Bid Addendum #4 Q: SCADA: Is it permissible to use L8 or L9 Rockwell ControlLogix instead of the specified L7? A: See Bid Addendum #4 Q: P&ID document states that not all valves are shown. Are the missing valves part of the controls narrative? Can we get more information about them? A: See Bid Addendum #4 Q: PLC&SCADA: System will involve PID control; how much control in the HMI will be required for these parameters? A: See Bid Addendum #4 Q: P&ID documents refer to PFxxx for Additional Process Flow Details. Where do these references exist? Does the Owner already have a list of setpoints/numerical requirements for the process flow control narrative in section 1.4? Or, do they want all of this to be adjusted from the HMI? A: See Bid Addendum #4 Q: BOM & SCADA: Are there any other documents that the Owner has that are available for review for a better understanding of desired outputs? A: See Bid Addendum #4 Q: 1. Detail 1 on sheet A504 refers to 2" rigid insulation and appears to point below the slab. Please confirm if this is the intent. 2. No mention of reinforcing in the concrete slab on grade has been found. Please clarify if the intent is to have an unreinforced slab. 3. Detail 2 on sheet S502 does not show any reinforcing. Please clarify what the intent is for this footing. 4. For the access stair to the tank/mezzanine, it's unclear whether the stair framing is steel with aluminum treads/landing/rail or fully aluminum. Please clarify. A: See Bid Addendum #4 Q: BOM - Master Control Panel Items 1. Can a Saginaw enclosure be quoted in lieu of the Hoffman enclosures? 2. BOM Item 2 missing part number. Please verify if this is to be A90SMP20. 3. BOM Item 21: a) Aluminum or Stell? b) Win 10 or Win 11? c) What Expansion Required? c1) One PCI or One PClex1? c2) Two PCI ce) Two PCle x 4? 4. BOM Item 31 missing part number. Please verify if it is to be 1756-N2 5. BOM Item 41 - part number is incorrect - missing the digit before the SC. Correct part number would look like EDS-316-?-SC. Our vendor advises that there are 18 options for this digit. Questions 1, 2, 4 & 5 also apply to the SCADA panel. BOM Item 22 NTE PN NTE5346 is no longer available. Please advise A: See Bid Addendum #4 Q: Mag meter spec calls for polypropylene liner material - McCrometer (approved manufacturer) uses 3M 135 Epoxy rated to 200 degrees F. Will this be acceptable? A: See Bid Addendum #4 Q: See below for some electrical questions: * How or why did they choose the Rockwell PLCs and Wonderware SCADA? o If Wonderware is important to them, we recommend System Platform, with InTouch OMI as the front end. * Any examples of what the HMI/SCADA system should look like? o Can more detail be provided for the requirements in section 2.3c o Is it expected that the SCADA will be accessible in any location outside of the specified HMI? o Will all control be handled by interfacing with the single HMI or are there control requirements for accessing SCADA outside of this location? * How many reports do they need? Do they have any examples of what they're looking for? * Are we using Wonderware InTouch instead of System Platform? o System Platform with AVEVA Historian is great with DreamReport, not sure about InTouch * Can we use L8 or L9 Rockwell ControlLogix instead of the L7 specified? * P&ID document states not all valves are shown. Are the missing valves part of the controls narrative? Can we get more information about them? * Are there any existing systems at this facility that we could get pictures of? * System will involve PID control, how much control in the HMI will be required for these parameters? * P&ID document refers to PFxxx for "Additional Process Flow Details", where do these references exist? * Does the client already have a list of setpoints/numerical requirements for the process flow control narrative in section 1.4? Or do they want all of this to be adjusted from the HMI. BOM Questions: Master Control Panel 1. Can we quote Saginaw enclosures as alternative to the Hoffman enclosures. 2. BOM ITEM 2 missing part number we think the part number is A90SMP20 3. BOM ITEM 21 - a. Aluminum or Stell b. WIN 10 or WIN 11 c. What expansion i. One PCI or One PCle x1 ii. Two PCI iii. Two PCle x 4 4. BOM ITEM 31 missing part number we think the part number is 1756-N2. 5. BOM ITEM 41-part number is incorrect missing the digit before the SC. Correct part number would look like this EDS-316-?-SC. Per our vendor there are 18 options. Queston 1,2, 4 and 5 also apply to the SCADA panel. BOM Item 22 NTE PN NTE5346, this part is no longer available. Propose the Crydom M50100 as a replacement? A: See Bid Addendum #4 Q: Specification Section 013300 - Contractor Submittals, 1.2 A(5) calls out for a shop drawing of the field office be submitted for approval per Spec Section 015200. The specifications do not include Section 01-5200. Question: Is a submittal for the field office trailer required? A: No, not required. Q: Please confirm the performance period of the contract for standard warranty purposes. The sample contract does not indicate this duration, nor do the Project Specifications - Section 01 77 00 Item 1.6 (references back to contract). Is it a one year or two year guarantee requirement? A: Construction window is estimated at 16 months. Warranty period will be for one year and begins upon issuance of the certificate of substantial completion. Q: 1.Is substitution of steel with a galvanized or powder coat finish for the handrails a suitable alternative to the anodized aluminum? a.Is substitution of a powder coat finish for aluminum in lieu of anodizing a suitable alternative for handrails? 2.Is substitution of steel with a galvanized or powder coat finish for the stairs a suitable alternative to the anodized aluminum? a.Is substitution of a powder coat finish for aluminum in lieu of anodizing a suitable alternative for stairs? 3.Is substitution of steel with a galvanized or powder coat finish for the ladder a suitable alternative to the aluminum? a.Is substitution of a powder coat finish for aluminum in lieu of anodizing a suitable alternative for ladders? 4.Is substitution of steel with a galvanized finish for the grating support embeds a suitable alternative to the stainless steel? 5.Is all hardware inside the building required to meet the corrosive service requirement? 6.What color of FRP grating is preferred? 7.Is substitution of square/rectangular tubing in lieu of pipe acceptable for the handrail design. 8.Is handrail designed and built by Axe Build a suitable alternate to the Wesrail system? 9.Is a mitered joint acceptable for the handrail continuous run system? 10.Specification section 05 50 00 3.1-B-5 states "Electrolysis protection of materials shall be provided." Is this requirement fulfilled by anodizing aluminum and galvanizing steel? If not, please explain. A: See Bid Addendum #4 Q: 1.) What are the specs on the pan decking for the mezzanine? There is nothing called out by the engineers that we can, see? 2.) GS014 Called out a W24 what is the size. 3.) HSS 6 x 6 x1/2 with a flange. Flange details? What is the tank? 4.) They are calling out to trim the angle to the grating depth. (Issues they want the angle galvanized, once dipped there is no grinding to fit.) loses the galvanizing. 5.) Can we pick a size and use the angle as a back stop for the concrete? 6.) GS011- Notes on #6 what are the treads. Pan with concrete, steel, etc.? need more details 7.) S401 - Mezzanine W24 is called out - what size. Are there more detailed drawings? 8.) What are the columns for the Mezzanine? Figure 2.1 shows a 6x6 are we to assume x 1/2. 9.) GS013 All gratings shall be steel. Is This Galvanized or stainless? There is an option for both. (Which do you want?) 10.) Is Grating flat, or knurled? 11.) On the table for gratings there are three different categories. Light, medium, and heavy. We cannot see where you want which size on the plans. 12.) On the grating supports there is more than one option, what option do you want. Angle, Or C Channel? 13.) Weld on studs, are those stainless, or steel that is galvanized? 14.) How do you want to attach the grating supports together? Is it okay if they just butt together? Mitered joints in the corner is all it calls out. 15.) On GS013 they are calling for angle with weld on studs that are 1/2" x 4", could we 3/8" x 4" instead. 16.) Do prevailing wages apply to any subcontractor that is manufacturing items out of state or off the job site and then install on the jobsite 17.) Regarding the comments below from previous addendum. It is not typical for the PEMB supplier to supply anchorage or stairs. I assume using alternate steel suppliers for this is acceptable, please advise. Answer The stairs shall be provided by the PEMB manufacturer; the way that the stairs are laid out is integral with the building and needs to be coordinated with the building framing. Third party for anchorage is acceptable. Stair detailing has been provided on a reissued Sheet A404. As noted on that sheet, the only part of the stairs that will not be provided by the PEMB manufacturer will be the site cast concrete to fill the metal pan stairs. The response we have been getting from PEMB's is as follows: PEMB's do not design/detail/supply Division 5 Metals, including but not limited to open framed stairs with open grating, closed stairs with concrete pans, handrail systems, guardrail systems, any miscellaneous steel that is embedded in concrete, etc. Will you need shop drawings for the stairs and is a fabricator okay to use for these? 18.) S109 calls out AL railing and ladder will other metals be acceptable for use? Galvanized, Powder Coated steel, etc..? 19.) Are Bollard sleeves acceptable instead of painted steel? 20.) Do you want the PEMB to be galvanized or will red Iron be acceptable? 21.) Can we get more information on all equipment and tanks going on the Mezzanine? Weights, what will be in tanks etc..? A: See Bid Addendum #4 Q: 1. Flowmeters and Flowmeter enclosures - There are multiple flowmeters shown in the PF sheet set that appear to be on below slab piping. Examples are FM-103, 203, 303, 403, 503, 603. These flowmeters do not appear to be shown in the corresponding M sheets. Detail M19 on GM008 notes an access hole with supported side walls with a removable access cover that appears it may be applicable to the above mentioned flowmeters. We have been unable to locate the materials of construction for this access hole. Please provide additional details of what is to be provided at the buried flowmeter locations. 2. Underslab Process Piping and Drains - In review of the process piping systems we have been unable to locate any details or requirements for concrete encasement of piping below building slabs and footings. Please confirm no concrete encasement is required for below slab process piping and drains. 3. Drawings M208 (RAS 3&4) and M307 (RAS 1&2) show a Removable Baffle Wall. Please provide details for the material required for the baffle walls, and size and how to install the baffle's. RAS 5&6 on drawing M407 does not show a baffle wall, please verify if this is correct. 4. RFB 26-0599 Bid Item Description, page 18. Please verify that all the procurement of the pipe for the yard piping and the interior piping within the building will be included in Bid Item No. 16 (Division 40 - Process Water Systems). Bid Item 15 (Division 33 - Utilities) includes the install of piping connections to the existing systems and septic upgrades. Connecting to the tanks, pumps, PVC and manhole. A: See Bid Addendum #4 Q: 1. Effluent Sump Stair System Specification Section 05 50 00, Paragraph 2.2 (Metal Stairs) indicates that all stairs shall be aluminum. However, structural drawings GS011 and GS012 indicate an option for either steel or aluminum construction. Please confirm that the following materials are acceptable for the Effluent Sump stair assembly: * Stair stringers and landing framing: Steel C12x20.7, hot-dip galvanized (HDG) after fabrication, per Sheet GS011 and project specifications * Stair treads and landings: Steel grating, HDG after fabrication * Guardrail and handrail: Aluminum, per Sheet GS012 and project specifications 2. Mezzanine Access Stair Addendum No. 2 added information to Sheet A404 indicating the mezzanine access stair is a steel stair with concrete pan-filled treads. Please confirm the following materials and scope are correct: * Stair stringers, landing framing, columns, etc.: Steel, HDG after fabrication * Stair treads: Concrete pan-fill type; steel pans HDG after fabrication * Guardrail and handrail: 8-line pipe guardrail; steel, HDG after fabrication * Design responsibility: This stair is a delegated design 3. Influent Treatment Tanks - Grating Support Beams Sheet S109 indicates W8x21 support beams at two locations to support the mid-span of the FRP grating. Please confirm these members are steel beams and are to be hot-dip galvanized after fabrication. 4. Equipment Opening Framing at Grating Reference Keynote 5/A109 and Keynote 4/S113, which indicate framing at equipment openings is to be designed and supplied by the grating manufacturer. Please confirm that steel angle or channel framing, hot-dip galvanized after fabrication, is acceptable for this application. A: See Bid Addendum #4 Q: Drawing M801, shows a Clay Distribution System (provided by Owner per Addendum #1), which appears to consist of Peristalic Pump, 140 Gallon Poly Tank, Air Diffuser Blocks, Regenerative blowers and RAS Booster Sump. These Clay Distribution Systems are located in RAS 1 & 2. Please provide specifications and/or details for these items to be able to understand how to install this equipment. A: See Bid Addendum #4 Q: Are press fittings allowed on copper lines? A: See Bid Addendum #4 Q: Who is the basis of design for the drum filters? A: See Bid Addendum #4 Q: RE: Pump Duty Points. Written spec vs the schedule does not match (flows mostly match, but TDH values are different). This has impact on final motor sizing, which will have other upstream implications (VFD sizing, conduit, etc). A: See Bid Addendum #4 Q: 1.How much will the liquidated damages be 2.GS001 Calls for a thermal coefficent of 1.2. Please confirm the building will be unheated. 3.Since the mezzanine is to be engineer and supplied by the PEMB mfg, please confirm the PEMB mfg can design the beams and columns instead of following what is currently drawn on page S401 4.There is no mention of the PEMB primary or secondary coating. Is this to be manufacturer standard or is a specific coating (galvanized, primed, etc) preferred? 5.FM Global is listed in the PEMB section of the specs. Is this facility insured by FM Global? If not, can this requirement be removed as it adds cost to the PEMB design to meet FM Global Requirements. If an FM engineer is assigned to the job, please provide their report for the design of the metal panel attachments to the girts. 6.The PEMB mfg does not engineer anchor rods typically. Please confirm whether the PEMB sub is to provide engineering for them or is the structural engineer to provide engineering based on PEMB reactions? A: Answer for 78-1; this is based on the amount of the contract, refer to Section 9.R of the sample contract. A: See Bid Addendum #4

    Key dates

    1. February 19, 2026Responses Due

    AI classification tags

    Frequently asked questions

    SLED stands for State, Local, and Education. These are solicitations issued by state governments, counties, cities, school districts, utilities, and higher education institutions — as opposed to federal agencies.

    SamSearch Platform

    Stop searching. Start winning.

    AI-powered intelligence for the right opportunities, the right leads, and the right time.