Closed Solicitation · DEPARTMENT OF VETERANS AFFAIRS

    4520--LYONS VAMC WATER HEATER REPLACEMENT BRAND SPECIFIC TO ENSURE HOOKUPS ARE COMPATIBLE NO ADDITIONAL PIPING BEING CONSIDERED

    DEPARTMENT OF VETERANS AFFAIRS
    Sol. 36C24226Q0588Sources SoughtALBANY, NY
    Closed
    STATUS
    Closed
    closed May 11, 2026
    POSTED
    May 4, 2026
    Publication date
    NAICS CODE
    333414
    Primary industry classification
    PSC CODE
    4520
    Product & service classification

    AI Summary

    The Department of Veterans Affairs is seeking sources for the replacement of water heaters at the Lyons VAMC. The opportunity includes specific models and features required for compatibility and performance. Interested vendors should review the detailed specifications provided for the Patterson-Kelley models PK-08D and PK-10D. This is a sources sought notice, not a request for proposals.

    Contract details

    Solicitation No.
    36C24226Q0588
    Notice Type
    Sources Sought
    Posted Date
    May 4, 2026
    Response Deadline
    May 11, 2026
    NAICS Code
    333414AI guide
    PSC / Class Code
    4520
    Primary Contact
    Corey Swinton
    City
    ALBANY
    State
    NY
    ZIP Code
    12208
    AI Product/Service
    product

    Description

    Qty 1 Patterson-Kelley Model PK-08D Semi-Instantaneous Water Heater rated to provide 27 GPM of Domestic Hot Water from 40-120F when supplied with 25 psig Inlet Steam and 5 psig in the Coil @ 1122#/hr. Heater to be furnished with the following features and controls to meet the specified demand: - Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working pressure. - Factory Insulation. - 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME working pressure and 210F test pressure. - All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz, with isolation valves, ball and check valves, and venturi tees. - 1 ½ Spence Pilot Operated, Self-Contained Steam Control Valve. - 1 ½ Wye Strainer. - ¾ ASME Temperature & Pressure Relief Valve at 150 psi. - ¾ ASME Pressure Only Relief Valve (Shipped Loose). - 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped Loose). - ½ Auxiliary Drip Tap (Shipped Loose). - ¾ Drain Valve Factory Installed. - Double Solenoid High Temperature Limit System with pre-wired control box. - Vertical Stand suitable for removal of heating section without disconnection of domestic water lines. - ¾ Vacuum Breaker Factory Installed. - 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge. - Operation & Maintenance Manuals in electronic form. - Factory Authorized Start-Up & Training Tags: 276458 (WH-2) Qty 1 Patterson-Kelley Model PK-10D Semi-Instantaneous Water Heater rated to provide 65 GPM of Domestic Hot Water from 40-140F when supplied with 40 psig Inlet Steam and 25 psig in the Coil @ 3469#/hr. Heater to be furnished with the following features and controls to meet the specified demand: - Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working pressure. - Factory Insulation. - 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME working pressure and 210F test pressure. - All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz, with isolation valves, ball and check valves, and venturi tees. - 2 ½ Spence Pilot Operated, Self-Contained Steam Control Valve. - 2 ½ Wye Strainer. - 1 ASME Temperature & Pressure Relief Valve at 150 psi. - 1 ½ ASME Pressure Only Relief Valve (Shipped Loose). - 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped Loose). - ½ Auxiliary Drip Tap (Shipped Loose). - ¾ Drain Valve Factory Installed. - Double Solenoid High Temperature Limit System with pre-wired control box. - Vertical Stand suitable for removal of heating section without disconnection of domestic water lines. - ¾ Vacuum Breaker Factory Installed. - 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge .

    Key dates

    1. May 4, 2026Posted Date
    2. May 11, 2026Proposals / Responses Due

    AI search tags

    Frequently asked questions

    4520--LYONS VAMC WATER HEATER REPLACEMENT BRAND SPECIFIC TO ENSURE HOOKUPS ARE COMPATIBLE NO ADDITIONAL PIPING BEING CONSIDERED is a federal acquisition solicitation issued by DEPARTMENT OF VETERANS AFFAIRS. Review the full description, attachments, and submission requirements on SamSearch before the response deadline.

    SamSearch Platform

    Stop searching. Start winning.

    AI-powered intelligence for the right opportunities, the right leads, and the right time.