Active Solicitation · DEPT OF DEFENSE

    CHEMICAL STORAGE BUILDING

    Sol. W911S226U3863Combined Synopsis/SolicitationSet-aside: Total Small Business Set-Aside (FAR 19.5)FORT DRUM, NY
    Open · 2d remaining
    DAYS TO CLOSE
    2
    closes Aug 7, 2026
    POSTED
    Jul 29, 2026
    Publication date
    NAICS CODE
    238290
    Primary industry classification
    PSC CODE
    5670
    Product & service classification

    AI Summary

    The Department of Defense is seeking proposals for the construction of a chemical storage building that meets specific safety and utility specifications. The building must include robust fire-rated designs, explosion-proof systems, and various safety features. Proposals must be submitted by August 7, 2026, for delivery to Fort Drum, NY.

    Contract details

    Solicitation No.
    W911S226U3863
    Notice Type
    Combined Synopsis/Solicitation
    Set-Aside
    Total Small Business Set-Aside (FAR 19.5)
    Posted Date
    July 29, 2026
    Response Deadline
    August 7, 2026
    NAICS Code
    238290AI guide
    PSC / Class Code
    5670
    Issuing Office
    W6QM MICC-FT DRUM
    Primary Contact
    Carrie Lawton
    State
    NY
    ZIP Code
    13602-5220
    AI Product/Service
    product

    Description

    The chemical storage building must meet several specifications for construction, safety, and utility. The required minimum dimensions are 42 feet in length, 8 feet in width, and 8 feet 3 inches in height. Access shall be provided by a 60-inch by 80-inch set of double doors, with at least one 36-inch active leaf, centered on one of the 42-foot walls and secured with a padlock-compatible handle. For spill containment, the building must include a sump with a minimum capacity of 1200 gallons.The structure must feature a robust fire-rated design, with walls tested by Intertek for a minimum 4-hour rating and a roof tested for a minimum 3-hour rating. Electrical specifications include a 12-space, 100-amp NEMA 3R main breaker panel (120V/240V), two Class 1, Division 2 explosion-proof LED light fixtures with a switch for the interior, and a dust/vapor-resistant exterior light with a photocell installed outside the hazard zone. Ventilation will be handled by an explosion-proof exhaust system rated for 335 CFM or higher, suitable for petroleum-based storage and compliant with all NFPA/UFC codes, complete with an indicator light and an emergency shut-off switch.For safety and functionality, the building shall be equipped with a grounding kit including an 8-foot ground rod, 10 feet of cable, and a clamp. The interior will be furnished with three-tier, 5-foot-long shelves that are 14 inches deep with a 2-inch lip. A non-perforated, skid-resistant steel ramp, measuring at least 52 inches wide by 72 inches long, must be included. Additionally, the unit shall come with three 10-pound ABC dry chemical fire extinguishers: two installed inside on either side of the door, and one mounted outside in a weatherproof cabinet. The completed chemical storage building is to be delivered to Building P-91, Railroad Street, Fort Drum, NY 13602.

    Key dates

    1. July 29, 2026Posted Date
    2. August 7, 2026Proposals / Responses Due

    AI search tags

    Frequently asked questions

    CHEMICAL STORAGE BUILDING is a federal acquisition solicitation issued by DEPT OF DEFENSE. Review the full description, attachments, and submission requirements on SamSearch before the response deadline.