Closed Solicitation · DEPARTMENT OF ENERGY

    TRANSFORMER OIL TESTING SERVICES

    DEPARTMENT OF ENERGY
    Sol. SS-260020346Sources SoughtSet-aside: Local Area Set-Aside (FAR 26.2)Princeton, NJ
    Closed
    STATUS
    Closed
    closed Nov 10, 2025
    POSTED
    Oct 29, 2025
    Publication date
    NAICS CODE
    541380
    Primary industry classification
    PSC CODE
    H291
    Product & service classification

    AI Summary

    The Department of Energy is seeking a qualified contractor to provide transformer oil testing services at the Princeton Plasma Physics Laboratory. The contractor will perform inspections, sample collection, and laboratory analyses of oil samples, including various ASTM standard tests. Interested parties should be prepared to offer additional analyses as needed.

    Contract details

    Solicitation No.
    SS-260020346
    Notice Type
    Sources Sought
    Set-Aside
    Local Area Set-Aside (FAR 26.2)
    Posted Date
    October 29, 2025
    Response Deadline
    November 10, 2025
    NAICS Code
    541380AI guide
    PSC / Class Code
    H291
    Primary Contact
    Jimmy Russell
    State
    NJ
    ZIP Code
    08540
    AI Product/Service
    service

    Description

    The Princeton Plasma Physics Laboratory is searching for a qulaified contractor to perform the following services

    Subcontractor shall perform the following tasks and provide associated documentation.
    5.1.1 Provide experienced personnel to inspect transformers and take required samples from oil
    filled transformers at PPPL at a mutually agreed upon time. All sampling containers and
    transport to subcontractors’ analyses facilities shall be provided by the subcontractor and
    include in the pricing schedule.
    5.1.2 Perform appropriate analyses of oil samples in subcontractor’s laboratory. Most samples will
    be mineral oil. Silicone and bio-based oils will be identified in the sampling plan (if part of
    routine analyses) or on individual samples. Transformers requiring these analyses will be
    identified by the PTR. Subcontractor may use alternate ASTM methods to those called out in
    the SOW.
    1. Oil Screen Analyses shall include the following.
    Analysis ASTM Standard
    a. Neutralization Number ASTM D 974
    b. Interfacial Tension (IFT) ASTM D 971
    c. Relative Density (Specific Gravity) ASTM D 1298
    d. Color ASTM D 1500
    PWR-SOW-056, Rev 2 PAGE 3 of 7
    e. Visual Examination ASTM D 1524
    f. Dielectric Breakdown Voltage ASTM D 877
    2. Moisture in Oil
    Analysis ASTM Standard
    a. Moisture in Oil ASTM D 1533
    3. Dissolved Gas Analysis
    Analysis ASTM Standard
    a. Dissolved Gas Sampling ASTM D 3613
    b. Analysis by Gas Chromatography ASTM D 3612
    4. Discretionary Analyses
    Subcontractor shall also offer other analyses on a sample by sample basis, including the
    following.
    Analysis ASTM Standard
    a. Oxidation Inhibitor ASTM D 2668
    b. Liquid Power Factor ASTM D 924
    c. Furan Content ASTM D 5837
    d. Metals in Oil ASTM D 3635
    5.1.3 Subcontractor may properly dispose of sample remains 6 months after analysis.

    Key dates

    1. October 29, 2025Posted Date
    2. November 10, 2025Proposals / Responses Due